XT2N 160 MA 20 Im=120...280 3p F F
ABBABB

XT2N 160 MA 20 Im=120...280 3p F F

36kA 3 Pole MCCB Magnetic

SKU: 1SDA067049R1

List Price

R 5 296,95

Excluding VAT · per unit

Key Specifications

Frame
XT2
Frame Current (Iu)
160 A
Rated Current (In)
20 A
Poles
3-Pole
Trip Unit
MA — magnetic adjustable
Mag. Trip Range (Im)
120–280 A
Overload Protection
None — downstream thermal relay required
Breaking Cap. (Icu)
36 kA
Rated Voltage
690 V AC
Standard
IEC/EN 60947-2

ABB XT2 MCCB with magnetic-only trip unit, 160 A frame, In = 20 A at 36 kA breaking capacity. Contains no thermal overload element — only an instantaneous magnetic release. Designed for motor feeder circuits where a downstream thermal overload relay is installed, and for transformer circuits where inrush current must not cause unwanted trips.

Features & Benefits

  • Rated current In = 20 A — magnetic-only protection, no thermal element
  • Adjustable magnetic trip Im = 120–280 A — set to motor locked-rotor current for precise protection
  • Coordinate with downstream thermal overload relay for full motor protection
  • 36 kA short-circuit breaking for demanding motor control centres

Technical Data

Poles
3
Rated Current
120 A

More in 36kA 3 Pole MCCB Magnetic