XT5S 400 TMA 400-4000 3p F F
ABBABB

XT5S 400 TMA 400-4000 3p F F

50kA 3 Pole MCCB Thermal Magnetic

SKU: 1SDA100415R1

List Price

R 15 149,48

Excluding VAT · per unit

Key Specifications

Frame
XT5
Frame Current (Iu)
400 A
Rated Current (In)
400 A
Poles
3-Pole
Trip Unit
TMA — both overload and instantaneous thresholds adjustable
Mag. Trip (Im)
4000 A
Breaking Cap. (Icu)
50 kA
Rated Voltage
690 V AC
Standard
IEC/EN 60947-2

ABB XT5 MCCB with thermal-magnetic protection, 400 A frame current, In = 400 A at 50 kA breaking capacity. The bimetal overload element provides inverse time-current overload protection while the magnetic element gives instantaneous short-circuit tripping.

Features & Benefits

  • Rated current In = 400 A — thermal-magnetic protection
  • TMA trip: both thermal and magnetic thresholds adjustable for precise coordination
  • 3-pole for standard 3-phase distribution and motor feeders
  • 50 kA breaking capacity — suitable for high fault-level LV systems

Technical Data